HT ITALIA – GSC57F

Multifunction device for verification of electric safety and mains analysis on single-phase and three-phase installations.

Multifunction device for verification of electric safety and mains analysis on single-phase and three-phase installations.
GSC57F is the first big multifunction device developed by HT! In a single device, all functions of the most advanced systems for safety testing; mains analyses, THREE-PHASE or SINGLE-PHASE (voltages, currents, powers, power factor, energies, etc.), voltage/ current harmonic analysis (up to the 49th) and an analysis of the anomalies on power supply voltages (dips, peaks); continuity test with test current 10A.
The device has a whole variety of functions and can be used with external feelers for measuring environmental parameters such as temperature/ humidity of air, illuminance (Lux) further to measuring leakage currents, Loop/Line impedance and calculating the assumed shortcircuit current with high resolution (0.1mOhm) in TN systems with the use of the optional accessory IMP57. Cutting-edge management of measurement with indication, at the end of each safety test, of compliance or non-compliance with requirements with simple symbols OK or NOT OK.

Need more information?

Please contact +6221-5467618, +6221-54212399 or email [email protected]

Specification

Continuity of protective conductors with 200mA / 10A 200mA/10A
Internal memory capacity 2MB
Indicative memory duration (in days @ PI=10min @ max number of parameters) 32 days
Recording with selectable integration period 5s-60m
Max number of simultaneously selectable parameters 64
Provided PC interface with software for Windows Optical / USB
Saving instant sampled values
AC/DC voltage and current in single-phase/three-phase systems
Insulation with voltage 50, 100, 250, 500, 1000VDC
Earth resistance by voltammetric method
Tripping time and current of RCDs type A, AC Standard, Selective
Voltage/current vector diagram
Voltage/current waveforms
Summary table of main electric parameters
Tables or histograms of Harmonics and THD%
Voltage and current harmonics up to the 49th with THD
Cosphi, Power Factor
Indicative memory duration (@ PI=10min @ max numb parameters)
Indication of recording duration
Active, reactive, apparent power/energy and DC power
  • CE MARK
  • CEI 64-8 612.6.2
  • CEI 64-8
  • CEI 64-8 612.3 .4 .5
  • CEI 64-8 612.6.1
  • CEI 64-8 612.6.3
  • CEI 64-8/7
  • EMC 2004/108/CE Directive
  • LVD 2006/95/CE Directive
  • DPR 462 del 22/10/2001
  • EN 61008
  • IEC/EN 61010-1
  • IEC/EN61557-1
  • IEC/EN61557-2
  • IEC/EN61557-3
  • IEC/EN61557-4
  • IEC/EN61557-5
  • IEC/EN61557-6
  • IEC/EN61557-7
  • VDE 0100
  • CEI 64-8 612.2
  • EMC: IEC/EN61326