HT ITALIA – SIRIUS89N

SIRIUS89N is the complete and versatile multifunction device developed starting from real installation needs. It has all of the functions of the most advanced systems for safety testing.

Multifunction device for verification of electric safety and mains analysis on single-phase installations

SIRIUS89N is the complete and versatile multifunction device developed starting from real installation needs. It has all of the functions of the most advanced systems for safety testing.

Single-phase mains analysis allows recording parameters such as voltages, currents, powers, power factor, energies, voltage/current harmonic analyses (up to the 49th) and analyzing the anomalies on power supply voltages (dips, peaks).

The device can be used with external feelers for measuring environmental parameters such as temperature/humidity of air, illuminance (Lux) further to measuring leakage currents, Loop/Line impedance and calculating the assumed short-circuit current with high resolution (0.1mOhm) in TN systems (with use of optional accessory IMP57), earth resistance, etc. Cutting-edge management of measurement with indication, at the end of each safety test, of compliance or non-compliance with requirements with simple symbols OK or NOT OK.

Need more information?

Please contact +6221-5467618, +6221-54212399 or email [email protected]

Specification

Insulation with voltage 50, 100, 250, 500, 1000VDC
Continuity of protective conductors with 200mA / 10A
Tripping time and current of RCDs type A, AC Standard, Selective
Non-trip earth resistance
Earth resistance by voltammetric method
Ground resistivity by 4-wire method
Loop/Line impedance, Phase-Phase, Phase-Neutral, Phase-PE
Loop/Line impedance Phase-Phase, Phase-Neutral, Phase-PE with high resolution (0.1mΩ)
Contact voltage
Phase sequence
Leakage current Through optional clamp HT96U
AC/DC voltage and current in single-phase/three-phase systems
Active, reactive, apparent power/energy and DC power
Voltage and current harmonics up to the 49th with THD
Voltage anomalies (dips, peaks) with a resolution of 10ms (@ 50Hz)
Cosphi, Power Factor
Max number of simultaneously selectable parameters 64
Recording with selectable integration period 5s-60m
Indicative memory duration (in days @ PI=10min @ max number of parameters) 32 days
Indication of recording duration
Internal memory capacity 2MB
Saving instant sampled values
Summary table of main electric parameters
Voltage/current waveforms
Tables or histograms of Harmonics and THD%
Voltage/current vector diagram
Measurement category CAT III 600V
Measurement with use of external TA and TV (with optional accessory HT903)
Measurement of air temperature (°C/°F), relative humidity (%UR) and illuminance (Lux)
Power supply 6×1.5V batteries type AA LR6
Auto power off
Provided PC interface with software for Windows Optical / USB
Size (LxWx H) (mm) 225x165x105
Weight in grams (batteries included) 1200
  • CE MARK
  • CEI 64-8 612.6.2
  • CEI 17-13/1
  • CEI 64-8
  • CEI 64-8 612.3 .4 .5
  • CEI 64-8 612.6.1
  • CEI 64-8 612.6.3
  • EMC 2004/108/CE Directive
  • LVD 2006/95/CE Directive
  • DPR 462 del 22/10/2001
  • EN 61008
  • IEC/EN 61010-1
  • IEC/EN61557-1
  • IEC/EN61557-2
  • IEC/EN61557-3
  • IEC/EN61557-4
  • IEC/EN61557-5
  • IEC/EN61557-6
  • IEC/EN61557-7
  • VDE 0100
  • CEI 64-8 612.2
  • EMC: IEC/EN61326