KYORITSU – 4200

The earth resistance from 0.05 to 1500Ω can be measured without the auxiliary earth spikes. (The Multiple Earthing System.)

  • The earth resistance from 0.05 to 1500Ω can be measured without the auxiliary earth spikes. (The Multiple Earthing System.)
  • True RMS
    Accurate true RMS readings of AC current including distorted waveform from 1mA to 30.0A
  • Noise Check Function
    A function to detect current, which effects on an earth resistance measurement and display “NOISE” mark on the LCD.
  • Memory function
    Save and display up to 100 measurement data.
  • Data hold function / Buzzer function / Back light function
    Compliant with Safety Standards of IEC 61010-1 : CAT IV 300V Pollution degree2
Need more information?

Please contact +6221-5467618, +6221-54212399 or email [email protected]

Specification

Function Range Resolution Measuring range Accuracy
Earth resistance Auto range 20Ω 0.01Ω* 0.00 – 20.99Ω |±1.5%±0.05Ω
200Ω 0.1Ω 16.0 – 99.9Ω |±2%±0.5Ω
100.0 – 209.9Ω |±3%±2Ω
1500Ω 160 – 399Ω |±5%±5Ω
400 – 599Ω |±10%±10Ω
10Ω 600 – 1580Ω
AC current
(50Hz / 60Hz)
Auto range
100mA 0.1mA 0.0 – 104.9mA |±2%±0.7mA
1000mA 1mA 80 – 1049mA |±2%
10A 0.01A 0.80 – 10.49A
30A 0.1A 8.0 – 31.5A
Operating system
Earth resistance function : Constant voltage injection,
Current detection,
(Frequency : Approx.2400Hz)
Dual Integration
AC current function : Successive Approximation
Over-range indication “OL” is displayed when input exceeds the upper limit of a measuring range
Response time Approx.7 seconds (Earth resistance)
Approx.2 seconds (AC current)
Sample rate Approx. 1 times per second
Power source DC6V : R6 (sizeAA manganese battery) × 4pcs,
or LR6 (sizeAA alkaline battery) × 4pcs
Current consumption Approx. 50mA (max. 100mA)
Measurement time Approx. 12 hours (when R6 is used)
Approx. 24 hours (when LR6 is used)
Auto power-off Turns power off about 10 minutes after the last button operation.
Applicable standards IEC 61010-1 : 2001 (CAT IV 300V Pollution degree2)
Withstand voltage AC5320Vrms / 5 seconds
Between the Transformer jaws fitted parts and Case enclosure
(except for jaws)
Conductor size Approx. 32mm max.
Dimension 246(L) × 120(W) × 54(D)mm
Weight Approx. 780g (including batteries)
Accessories Battery R6 (AA) × 4, Instruction manual
8304 (Resister for operation check)
9166 (Hard case)