KYORITSU – 3007A

  • Bargraph to display insulation resistance.
  • Displays the value of external AC voltage along with flashing symbol.
  • Bargraph to display insulation resistance.
  • Displays the value of external AC voltage along with flashing symbol.
  • Auto null function to automatically subtract the test lead resistance before displaying the real continuity resistance value.
  • Trac-Lok mode to conserve battery life on insulation and continuity tests.
  • Live circuit warning beeper.
  • Releasing the test button automatically discharges the charges stored in the circuit under test.
  • Backlight function to view the test results in dimly lit areas.
  • 200mA continuity measuring current to IEC 61557.
  • Minimum 1mA current on insulation tests to IEC 61557.
Need more information?

Please contact +6221-5467618, +6221-54212399 or email [email protected]

Specification

Insulation Resistance
Test Voltage 250V/500V/1000V
Measuring Ranges
(Mid-scale Value)
20MΩ/200MΩ/2000MΩ
Output Voltage
on open circuit
Rated test voltage+20%, -0%
Nominal Current 1mA DC min.
Output Short
Circuit Current
1.5 mA DC approx.
Accuracy |±1.5%rdg±5dgt (20MΩ/200MΩ)
|±10%rdg±3dgt (2000MΩ)
Continuity Test
Measuring Ranges
(Mid-scale Value)
20Ω/200Ω/2000Ω
Output Voltage
on open circuit
7 – 12V DC
Measuring Current 200mA DC min.
Accuracy |±1.5%rdg±5dgt (20Ω)
|±1.5%rdg±3dgt (200Ω/2000Ω)
AC Voltage
AC Voltage range 0-600V AC
Accuracy |±5%rdg±3dgt
General
Safety Standard IEC 61010-1 CAT III 300V Pollution Degree 2
IEC 61010-2-031 IEC 61557-1/2/4
IP Rating IEC 60529-IP54
EMC Standard IEC 61326-1
Withstand Voltage 3700V AC for 1 minute
Power Source R6 (AA) (1.5V) × 8
Dimensions 185(L) × 167(W) × 89(D)mm
Weight 990g approx
Accessories 7122B (Test leads) Pouch for test leads
8923 (F500mA/600V fuse) × 2
R6 (AA) × 8
Shoulder Strap
Instruction Manual

Downloads